Real power P is the time-average rate of energy transfer, measured in watts. Apparent power S combines RMS voltage and current, measured in volt-amperes. For sinusoidal conditions, reactive power Q describes the quadrature component, commonly reported in var.
These quantities can share equivalent base dimensions while describing different aspects of an AC load. Their labels should remain distinct.
Single-phase sinusoidal relations
With RMS voltage V and current I and phase angle φ:
S = VI
P = VI cosφ
Q = VI sinφ.
Under the common passive-load convention, lagging current for an inductive load corresponds to positive Q and leading current to negative Q. State the convention when a signed value matters.
For sinusoidal single-frequency conditions, S² = P² + Q² and power factor equals cosφ. Tektronix's AC-power fundamentals explains these relations and the distinction between real and apparent power.
Original single-phase example
Assume V = 230 V RMS, I = 10 A RMS and lagging power factor 0.80 with sinusoidal waveforms. Apparent power is 2,300 VA. Real power is 1,840 W.
The corresponding reactive power magnitude is 2300 sqrt(1 − 0.8²) = 1380 var. The phase angle is about 36.9 degrees. A resistive load drawing the same 10 A would have a different real power because its power factor would be unity under the ideal sinusoidal model.
These are supply-side electrical quantities. A motor's mechanical output power would additionally account for motor efficiency at that operating point.
Balanced three-phase relations
For a balanced sinusoidal three-phase system with line-to-line RMS voltage VLL and line RMS current IL:
S = sqrt(3) VLL IL
P = sqrt(3) VLL IL cosφ
Q = sqrt(3) VLL IL sinφ.
Using 400 V line-to-line, 8 A line current and power factor 0.85 gives about 5.54 kVA apparent power and 4.71 kW real power. Do not use a line-to-neutral voltage in the same expression without changing the formula.
An unbalanced system requires phase-by-phase treatment or an appropriate measurement method, rather than assuming the balanced expression still applies.
Distorted waveforms change the interpretation
Real power remains average[v(t)i(t)]. Apparent power is based on RMS voltage and current under the chosen system definition, and true power factor is P/S.
With harmonic distortion, true power factor is not generally equal to the cosine of the fundamental phase displacement. Likewise, sqrt(S² − P²) is a non-active power magnitude and cannot always be interpreted as signed sinusoidal reactive power.
Tektronix's three-phase motor-drive primer discusses the difference between full-waveform measurements and sinusoidal shortcuts.
Keep measurement conditions with the result
Use RMS rather than sine-wave peak values. Record frequency, waveform quality, phase connections and whether the power represents one phase or the complete system.
Use the AC-power calculator with a matching circuit model. The electrical-unit guide provides additional checks on units and measurement definitions.